Main technical characteristics of PLC-DО-24 output discrete signals module:
| Name of Parameter | Unit of measurement | Value |
| Number of discrete outputs | - | 24 (one galvanically isolated group) |
| Rated output voltage, DC | V | 24 |
|
Output DC, max: |
mA |
|
| Output overload protection actuation current, DC | А | 1.4 – 2.0 |
| Output resistance of public key, max. | mΩ | 165 |
| Private key leakage current, max. | uA | 20 per channel |
| Current of load failure monitoring generator | uA | 80 per channel |
| Maximum output switching frequency | kHz | 1 |
| Electrical insulation resistance of galvanically isolated circuits (upon test voltage frequency 50 Hz and testing time 1 min.) | V | 1000 |
| Electrical insulation resistance of galvanically isolated circuits (at U test = 1000 V DС), min. | MОhm | 100 |
| Module address setting from 0 up to 15 | - | mechanical switching device |
| Interface of communication with master controller | - | RS-485 (Modbus-RTU Slave up to 115200 bps or CAN (from 50 kHz up to 500 kHz) |
| Connection/disconnection of matching resistance of connection line 120 Om | - | configured with a parameter |
| Module power supply voltage in +24 V DC circuit | V | 10 – 34 |
| Module power supply voltage in +5 V DC circuit | V | 4.7 – 5.5 |
| Consumption power in +5 V circuit | W | 0.5 |
| Environmental conditions | ||
| Operational temperature | °C | from -20 up to +45 |
| Storage temperature | °C | from -40 up to +60 |
| Relative humidity | - | up to 80 % with no condensed water |
| Atmospheric pressure | kPa | from 86 up to 106 (645 – 795 mm Hg) |
| Operation mode | - | continuous |
| Cooling | - | natural |
| Type of installation | - | DIN rail, 35 mm |
| Protection level EN 60529:2014 | - | IP 20 |